There's Gold in the Air Power Equation
The mathematics for properly designing ventilation
and emission control systems have been around for quite awhile, but our studies
of hundreds of systems show that many are wasting energy, while still lacking
capacity to meet applicable codes and process objectives.
There's a lot of money on the table in operating
costs for these systems. More than 40% of the energy consumed in most
manufacturing plants is used to power fans, pumps and ventilators. In some
cases, the annual operating costs of a system may actually exceed the initial
capital cost within two years of installation. Opportunities for improvement
reside in the air power equation.
Power required for an air handling system is
computed with the following factors:
- Volumetric Flow Rate "Q", stated in ft3/min (cubic
feet per minute)
- Total Pressure (resistance due to friction in ducts,
hoods and ĘP of control device, etc.) "TP" stated in inches of water ("H20)
- Density factor of the gas being collected "df"
(dimensionless),
- Efficiency of the fan, "n" (dimensionless).
These are combined into the Air Power Equation:
Power (horsepower) = [(Q)(TP)(df)] / (n)(6356)
Small reductions in the numerator can have a
significant cost impact. For example, a typical 20,000 CFM baghouse requires 60
or more horsepower for operation. A reduction of 1000 CFM with improved hood
design, or reduction of 1 inch static pressure with an improved duct or baghouse
system, can save as much as $4,000 per year.
There are always limits on what can be done,
however. The process may require a certain airflow or hooding arrangement, and
that will dictate air volume. Adjustments to system pressure and fan efficiency
may be better places to effect reductions.
System pressure is usually affected by two
factors:
- Hood and duct resistance as a function of velocities
in the system and the inefficiencies of flow (poorly designed hoods, short
radius elbows, branch entry angles greater than 45”, abrupt contractions, and
elbows and other interferences at fan inlets and outlets - called Fan System
Effects, etc.)
- Resistance across the emission control device. A baghouse that operates at a pressure drop of 8 inches H2O will require twice the
power of a collector operating at 4 inches H20. However, the lower pressure drop
collector may not provide the capture efficiency of the baghouse with higher
pressure drop. Of course you can lower the pressure drop in a baghouse by adding
filter area, but this means a larger housing. More important, baghouses often
perform best at high pressure drops. The key is to minimize pressure drop while
still meeting emission requirements. Excess static pressure just wastes power.
Here are some tips to help find that narrow range
of safe and efficient operation.
- Minimize Flow: Systems directly connected to a
process source are inherently volume-limited, whereas systems that capture
emissions with enclosures or hoods need to be optimized during the design
process. Total enclosure of an emission source minimizes air flow and worker
exposure. However, such enclosures can restrict visual observation of the
process and hinder maintenance access.
Hoods that cannot be designed for total enclosure
should be located as close to the source as possible. A side draft hood (Figure
1) located twice the distance from the source can require as much as four times
the exhaust volumetric flow rate as a total enclosure. Capture hoods for
high-velocity emissions (from grinding, sawing, etc.) must be located so the
opening is in the direct path of the dust, fume or mist. The American Conference
of Governmental Industrial Hygienists publication Industrial Ventilation - A
Manual of Recommended Practice provides guidelines for good design of hoods,
duct and similar equipment.
Other factors such as explosive limits for the gas
being collected, moisture content (dew point) and heat content may influence the
air volumetric flow rate requirements so there may be limits to the
optimization.
- Minimize Pressure: Pressure offers greater
opportunities to reduce energy costs. A system with good airflow characteristics
(duct velocities and sizes optimized), matched with the proper control device,
pressure monitors and variable frequency drives, can help manage system
pressure. Most bag houses or other collection devices will have varying pressure
drops over the life of the system. Bags are generally more efficient at higher
pressure drop, but then use more energy. Scrubbers, oxidizers and electrostatic
precipitators tend to operate at more constant resistance. A good pressure
monitoring system that controls system volumetric flow rate can save thousands
of dollars every year on the operation of even medium sized systems. As variable
frequency drives become less expensive they are now being found on many
installations, especially systems of over 10,000 CFM.
Be mindful of duct inefficiencies and Fan System
Effects (elbows at inlets and outlets, etc.). These shortcuts increase static
pressure and operating costs for the life of the system. Figure 2 shows
short-radius elbows and system effects that would add $6500 per year in wasted
power in this example.
- Control Density: Temperature, moisture,
molecular weight, elevation and the absolute pressure in the duct or vessel
affect the density of the transporting gas. A density change may affect the
hardware requirements for the system. Evaporative cooling, for example, reduces
volume, but the higher density air requires more power. This may be more than
offset by reduced costs for smaller ducts, control devices and fans (as well as
lower the value for volumetric flow rate in the equation). Cooler temperatures
may also allow use of less expensive collectors, fans and peripheral devices.
- Fan Efficiency: The design of the fan and its
blade type can greatly affect efficiency and power requirements.
Laboratory-measured peak fan efficiency may not be the most stable point of
operation. If peak efficiency coincides with the peak of the pressure curve then
there may be operational problems as volumetric flow rates vary with small
changes in system pressure. The designer must consider both curves when
selecting the best fan and operating point to optimize reliability and power
usage. And fan type may dictate proper selection. Airfoil wheels, while more
efficient, may not be a good choice when handling particulate-laden air.
The key to any design is proper fan selection.
Figure 3 illustrates the importance of matching the fan to the system, as
calculated. Any of the three improper matches waste power and produce
unsatisfactory system performance.
Summary
The power equation identifies four main areas -
volumetric flow rate, pressure, density and fan efficiency - that affect energy
consumption. The challenge for industry is to operate in the narrow functional
range that guarantees system effectiveness with minimum energy consumption.
Attention to the Air Power Equation can help meet those goals.
Authored by Gerry Lanham, P.E.,
President, KBD/Technic,
Inc.
For more information contact:
KBD/Technic Inc.
3131 Disney St.
Cincinnati, OH 45209
513-351-6200
Fax: 513-351-4071